Common Specifications of Main Units
Classification | Item | Specification |
Signal Output | Converted Output | DC4-20mA、1 Output (Response time 3 sec*1) |
Monitor Output | AC±5V FS±5%(for quick check)*3 1-5VDC FS±5%(option) |
Alarm Output | Alarm Contact | 1 Step 1a Contact AC 125V、 DC 30V-1A (Resistive Load) |
Alarm Level Setting Extent | 0~100% of Full Scale Arbitrary Setting (in 1% Step)*2 |
Alarm Action | Detecting the set Alarm level ,activates at the end of the Delay time (reset automatically) Initial Delay time setting 5sec (3~99sec: 1 sec Step) |
Indication | Main Unit Panel Indicator | Red 7 segment LED (4 Digit Indication) |
Vibration Amplitude | 5 Ranges for each selected function Blinks for over 120% of Full Scale |
Alarm Setting (%) | 1~100% for Full Scale*2 |
Pickup Sensitivity | 80~120% for Standard Sensitivity |
Ambient Environment | Ambient Temperature | -5~55℃ |
Ambient Humidity | 30~90%RH(No condensation) |
Others | Supply Voltage | AC100V±10% 50/60Hz±2Hz |
Installation | On the Wall or DIN Rail (Din Rail contact section is demountable)On |
Terminal Board | M3.5 screws on the Back Panel |
Outward Case Material | Plastic |
Size・Mass | W50×H80×D127mm Approx. 300g |
*1:Changeable by the customized software
*2: Setting of 0% cancels the alarm function.
*3:Usable for quick check of the waveforms
(1)Specifications of VM-90 DA (Applicable to Pre-amplifier build-in type Pickups)*6(VP-A51 IW / VP-A 4345Ⅰ)
Measurement Mode | Item | Specification |
Acceleration*5 | Measurement Range | 10, 20, 50, 100, 200(m/s2rms) |
Frequency Range | 10~4kHz±1dB 10~10kHz+1dB、-3dB |
Velocity*5 | Measurement Range | 5, 10, 20, 50, 100(mm/s rms) |
Frequency Range | 10~1kHz+1dB、-2dB |
H Function*5 | Measurement Range | 10, 20, 50, 100, 200(m/s2rms) |
Frequency Range | DC~1kHz(Envelope detection of 2kHz~15kHz) |
H Function CF*5 | Measurement Range | 5, 10, 20, 50, 100 |
Frequency Range | DC~1kHz(for peak/rms of H Function) |
*5:Changeover of the measurement mode is possible by the switch located on the front panel.
*6:Designate the type of the main unit on placing order
(2)VM-90 DV Specifications (Using Medium Frequency Pickups)*6(VP-90 VC / VP-90 VD)
Mode | Item | Specification |
Velocity*5 | Measurement Range | 5,10,20,50,100(mm/s rms) |
Frequency Range | 10~1kHz+1dB |
Displacement*5 | Measurement Range | 50,100,200,500,1000(μmp-p) |
Frequency Range | 10~500Hz±1dB |
*5:Changeover of the measurement mode is possible by the switch located on the front panel.
*6:Designate the type of the main unit on placing order
(3)VM-90 DV Specifications (Using Low Frequency Pickups)*6 (VP-91 VC / VP-91 VD / VP-92 VC / VP-92 VD)
Mode | Item | Specification |
Velocity*5 | Measurement Range | 5,10,20,50,100(mm/s rms) |
Frequency Range | 5~500Hz+1dB |
Displacement*5 | Measurement Range | 50,100,200,500,1000(μmp-p) |
Frequency Range | 5~500Hz±1dB |
*5:Changeover of the measurement mode is possible by the switch located on the front panel.
*6:Designate the type of the main unit on placing order